Redox (ORP) Transmitters

 
 

HI 8615 & HI 8615L (LCD readout)  


click on photo
to enlarge
 
Technical Data
 
  HI 8615 & HI 8615L HI 8615L only
Range 4 to 20 mA 0.00 to 14.00 pH
Resolution 0.01 mA 1 mV

Accuracy @ 20%C

± 0.02 mA ± 5 mV
Calibration Zero : ± 0.8 mA
Slope : ± 0.8 mA
Zero : ± 100 mV
Slope : 90-110%
Input Impedance 1012 ohms
Output 4 to 20 mA Isolated
Protection IP 65
Power Supply without LCD : 12 to 30 VDC /
with LCD : 17 to 36 VDC
Load Max. 500 ohms

 